Customization: | Available |
---|---|
Electricity Type: | AC |
Number of Pole: | 8 |
Still deciding? Get samples of US$ 833.3/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Range | TeSys |
---|---|
Product name | TeSys T |
Device short name | LTMR |
Product or component type | Motor controller |
Device application | Equipment monitoring and control |
Measurement current | 5…100 A |
[Us] rated supply voltage | 100...240 V AC 50/60 Hz |
Current consumption | 8...62.8 mA |
Supply voltage limits | 93.5…264 V AC |
Communication port protocol | Modbus TCP/EtherNet/IP |
Bus type | Ethernet IEEE 802.3 interface, addressing 0...159, transmission rate 10...100 Mbit/s, RJ45 with 2 shielded twisted pairs |
[Ui] rated insulation voltage | 690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508 |
[Uimp] rated impulse withstand voltage | 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1 |
Short-circuit withstand | 100 kA conforming to EN/IEC 60947-4-1 |
Associated fuse rating | 4 A gG for output 0.5 A gG for control circuit |
Protection type | Reverse polarity protection Overload Phase unbalance Overload (long time) Thermal protection Power factor variation Thermal overload protection Locked rotor Earth-leakage protection Load fluctuation Phase failure |
Network and machine diagnosis type | Waiting time after overload tripping Motor control command recording Trip context information Phase fault and earth fault trip counters Starting current and time Trip history information Fault recording Event recording Remaining operating time before overload tripping Running hours counter/operating time |
Logic input number | 6 |
Input current | 3.1 mA at 100 V 7.5 mA at 240 V |
Current state 0 guaranteed | Logic input: 0...40 V and <= 15 mA for 25 ms |
Current state 1 guaranteed | Logic input: 79...264 V and >= 2 mA for 25 ms |
maximum output switching frequency | 2 Hz |
Load current | 5 A at 250 V AC for logic output 5 A at 30 V DC for logic output |
Permissible power | 480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output) |
Maximum operating rate | 1800 cyc/h |
Contacts type and composition | 1 NO + 1 NC fault signal 3 NO |
Metering type | Phase current I1, I2, I3 RMS Temperature Earth-fault current Average current Iavg Imbalance current |
Measurement accuracy | 5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 5 % active and reactive power 0,02 current |
Overvoltage category | III |
Connection pitch | 5.08 mm |
Connections - terminals | Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end |
Tightening torque | Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm |
Pollution degree | 3 |
Electromagnetic compatibility | Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 |
Q: How about the warranty?
A: We provide 12 months warranty for all the items we offer, you can return any item with quality problem within 15 days.
Q: Other suppliers are better than yours.
A: "Create more benefits for customers" is our belief, if you have a better price, please let us know, we will try our best to meet your price and support you.
Q: What about delivery?
A: We have DHL freight forwarders with competitive prices, of course customers can also use their own freight forwarders.
Tested New 100%original Hold In Stock PLC Module Quality And Best Price
Q: How about the technical support?
A: With our professional technology, we can help customers to solve some technical problems.